Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T07CM04551
Parcel: 99999999A

Address:
3545 N 1ST AV

Review Status: Completed

Review Details: OTHER

Permit Number - T07CM04551
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/06/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the required provisions for expansion compensation for the pipe on the drawing. Provide calculations.
2. Revise the font size to 1/8" minimum (M12).
3. Show the locations for the air vents and drains.
4. Provide the installed weight of the individual fan coils.
12/06/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM04551 12/6/07

Address electrical circuiting, overcurrent protection, disconnecting means, and loads. For example, if the new Fan Coils are identical in voltage and current draw to those which are existing, and the intent is to reuse all existing electrical components, this shall be clear from the plans.