Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T07CM04551
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/06/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show the required provisions for expansion compensation for the pipe on the drawing. Provide calculations. 2. Revise the font size to 1/8" minimum (M12). 3. Show the locations for the air vents and drains. 4. Provide the installed weight of the individual fan coils. |
12/06/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM04551 12/6/07 Address electrical circuiting, overcurrent protection, disconnecting means, and loads. For example, if the new Fan Coils are identical in voltage and current draw to those which are existing, and the intent is to reuse all existing electrical components, this shall be clear from the plans. |