Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM04544
Parcel: 125150850

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T07CM04544
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2008 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 1/25/08
Activity: T07CM04544
Address: 25 E. Calle Encanto
Applicant: Todd Rutledge

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

FLOOR PLANS:
3. Specify use of existing rooms on upper floor that adjoin the addition.

STRUCTURAL PLANS:
4. Provide an attic space ventilation calculation and note the size and location of all attic vents needed to comply, R806.2.

SECTIONS - DETAILS:
5. Specify vapor barrier behind brick veneer, R703.2 & R703.7.
6. Show 1" air space between sheathing and veneer R703.7.4.2.

PLUMBING PLAN:
7. Provide the maximum developed length of water line from the meter the furthest appliance served, and the diameter of the water line, UPC Table 6-6.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/07/2008 DELMA ROBEY APPROVAL SHELF Completed
02/07/2008 DELMA ROBEY OUT TO CUSTOMER Completed
02/07/2008 DELMA ROBEY REJECT SHELF Completed