Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM04541
Parcel: 13507444E

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T07CM04541
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/21/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T07CM04541 4/15/08

1. Plumbing calls for WH on Main Level only. Electrical calls for WH on both Main Level and Mezzanine. Please clarify.
2. Plumbing calls for 4500W WH. Electrical accounts for 2500W. Clarify.
3. Mechanical specifies 25A maximum breaker size for AC. Electrical provides 30A. Coordinate with Mechanical and clarify.
04/21/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/21/2008 DELMA ROBEY APPROVAL SHELF Completed
04/21/2008 DELMA ROBEY OUT TO CUSTOMER Completed
04/21/2008 DELMA ROBEY REJECT SHELF Completed