Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/15/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
04/21/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T07CM04541 4/15/08 1. Plumbing calls for WH on Main Level only. Electrical calls for WH on both Main Level and Mezzanine. Please clarify. 2. Plumbing calls for 4500W WH. Electrical accounts for 2500W. Clarify. 3. Mechanical specifies 25A maximum breaker size for AC. Electrical provides 30A. Coordinate with Mechanical and clarify. |