Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04541
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/05/2007 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 12/05/2007 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 12/06/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM04541 12/6/07 1. Ckt A-2 appears to account for the track lighting only on the panel schedule. 2. Water Heater is 3KW on Plumbing Plans, but Electrical only accounts for 2.5 KW. Coordinate with Plumbing and clarify. 3. One electrical circuit on the Main Level Power Plan does not have Panel/Circuit designation. 4. Could not find "Control Credit Watts" in 2006 IECC. Willing to discuss. |
| 12/06/2007 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/12/2007 | VFLORES1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 12/12/2007 | VFLORES1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 12/12/2007 | VFLORES1 | WATER | REVIEW | Needs Review | |
| 12/12/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/12/2007 | VFLORES1 | WWM | REVIEW | Needs Review | |
| 12/12/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |