Permit Number: T07CM04541
Parcel: 13507444E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04541
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2007 TERRY STEVENS ZONING REVIEW Approved
12/05/2007 LOREN MAKUS ENGINEERING REVIEW Approved
12/06/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM04541 12/6/07

1. Ckt A-2 appears to account for the track lighting only on the panel schedule.
2. Water Heater is 3KW on Plumbing Plans, but Electrical only accounts for 2.5 KW. Coordinate with Plumbing and clarify.
3. One electrical circuit on the Main Level Power Plan does not have Panel/Circuit designation.
4. Could not find "Control Credit Watts" in 2006 IECC. Willing to discuss.
12/06/2007 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/12/2007 VFLORES1 MECHANICAL-COMMERCIAL REVIEW Needs Review
12/12/2007 VFLORES1 PLUMBING-COMMERCIAL REVIEW Needs Review
12/12/2007 VFLORES1 WATER REVIEW Needs Review
12/12/2007 DAVE MANN FIRE REVIEW Approved
12/12/2007 VFLORES1 WWM REVIEW Needs Review
12/12/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review