Permit Number: T07CM04536
Parcel: 10609025A

Address:
3660 N ROMERO RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04536
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2008 HEATHER THRALL ZONING REVIEW Needs Review
01/11/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Interlocking the restroom exhaust fans with the lights will allow the supply air to the restrooms to be recirculated. Reference Section 403, IMC 2006.
2. Provide calculations to show that the temperature of the assembly room can be maintained at 68 degrees Fahrenheit on a design winter day. Reference Section 309.1, IMC 2006.
01/11/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t07cm04536 1/11/07

1. Identify all exterior lighting fixtures on Lighting Plan.
2. Put Unit Heater on Ckt A-32 on the panel schedule.
3. Provide cut sheets for all exterior lighting fixtures.
4. Provide electrical requirements for the heat pump.
5. The heat pump, at 28.2 KVA per phase, would draw 235A. But this is a 30A circuit. Please clarify.
6. Panel schedule appears to be set up for KVA, not VA. Please clarify "VA per Phase" designation.
7. Show the location of Panel A on the plans.
8. Provide a statement describing the anticipated activities at this location.
01/11/2008 ROBERT SHERRY WATER REVIEW Approved Water demand 12 GPM
01/11/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. NEED SERVICE SINK AT 2'-10" FOR H/C ACCESSIBILITY
2. NEED BO APPEALO FOR WATER DISPENSER
01/11/2008 JASON GREEN ENGINEERING REVIEW Needs Review
01/11/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The temperature and pressure relief shall not terminate into the tailpiece of a sink.
2. Provide a riser diagram for the revised waste and vent piping.
3. Show that the existing 3/4" water supply pipe can accomodate the proposed water demand.
01/11/2008 DAVE MANN FIRE REVIEW Approved
01/11/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/22/2008 CAGUILA1 WWM REVIEW Needs Review