Permit Number: T07CM04536
Parcel: 10609025A

Address:
3660 N ROMERO RD

Review Status: Completed

Review Details: SITE

Permit Number - T07CM04536
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2008 DAVE MANN FIRE REVIEW Approved
01/11/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the site drawing to show the location of the public sewer and the proposed point of connection for the building sewer. Reference Section 103.2.3, UPC 2006.
2. Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson.
01/11/2008 JASON GREEN ENGINEERING REVIEW Approved
01/22/2008 PETER MCLAUGHLIN NPPO REVIEW Passed
01/22/2008 STEVE SHIELDS ZONING REVIEW Approved
01/22/2008 STEVE SHIELDS ZONING HC SITE REVIEW Approved
01/22/2008 PETER MCLAUGHLIN LANDSCAPE REVIEW Approved