Permit Number: T07CM04536
Parcel: 10609025A

Address:
3660 N ROMERO RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04536
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2008 CAGUILA1 ZONING REVIEW Needs Review
01/11/2008 CAGUILA1 WWM REVIEW Needs Review
01/11/2008 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
01/11/2008 CAGUILA1 ENGINEERING REVIEW Needs Review
01/11/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
01/11/2008 CAGUILA1 FIRE REVIEW Needs Review
12/05/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide specifications for both the existing and the new heat pump.
2. Show the proposed duct layout and the duct sizes.
3. Specify the required duct insulation.
4. Provide balancing and ventilation data.
12/05/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a clear scope of work for the plumbing work.
2. Provide the specifications and an installation detail for the water heater.
12/05/2007 ROBERT SHERRY WATER REVIEW Denied Provide the size and location of the existing water meter along with the existing (?) backflow preventer.
12/05/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied NEED ARCHITECT TO COMPLETE CODE REVIEW AND REQUIREMENTS. PLANS TO BE SUBMITTED FOR CHECKING.