Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2008 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Activity: T07CM04635
Date: 1-07-08

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

I. GENERAL REQUIREMENTS:
" Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

II. STRUCTURAL PLANS:
" Truss calculations must be signed, dated and wet-sealed by an engineer who is registered in Arizona. Truss calculations shall be cross-referenced to the floor plans. Note the requirement for a deferred submittal if the truss calculations will not be submitted with the plan review.

III. PLUMBING PLAN:
" Provide 4" vent to roof on plumbing layout in kitchen area for Chicago vent detail.
" Location of clean-out at sewer tie-in point must be positioned to allow cleaning in the direction of flow, UPC 707.6.
" Specify the size of existing water meter, UPC Table 6-6.

IV. OUTDOOR LIGHTING CODE
" Full-cut-off fixtures allow no candela to occur at or above an angle 90 degrees above the nadir. Adjustable fixtures and perforated shields do not comply, ODL 4.7.

V. INTERNATIONAL ENERGY CONSERVATION CODE:
" Specify the solar heat gain coefficient of all new windows, N1102.1.

If you have any questions please contact:
Clayton Trevillyan
(520) 837-4913
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/08/2008 CINDY AGUILAR OUT TO CUSTOMER Completed