Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM04511
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/12/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PLEASE PROVIDE COPY OF SHOPPING CENTER SITE PLAN SHOWING ACCESSIBLE ROUTES FROM PUBLIC TRANSPORATION AND ACCESSIBLE PARKING TO FRONT ENTRANCE OF SPACE AND SPECIFY ACESSIBLE ROUTE SLOPES. 2. PLEASE PROVIDE AN ACESSIBLE TOILET ROOM AS PER REQUIREMENTS OF 2006 IBC, SECTION 2902.4 (CAN NOT ACCESS TOILET ROOM THROUGH A STORAGE SPACE) 3. PLEASE PROVIDE AN ACCESSIBLE WATER FOUNTAIN AS PET 2006 IBC, SECTION 1109.5.1 AND ANSI 117.1, SECTION 602.4 (DUAL HEIGHT SPOUTS) 4. PLEASE SURVEY EXISTING TOILET ROOM AS TO FULL ACCESSIBLE REQUIRMENTS AND PROVIDE A STATEMENT ON THE DRAWINGS CERTIFYING THAT THE EXISTING TOILET ROOM MEETS ALL 2006 IBC PLUS ANSI 117.1 ACCESSIBLE REQUIREMENTS OR PROVIDE FLOOR PLAN AND ALL INTERIOR ELEVATIONS SHOWING COMPLIANCE. 5. PLEASE PROVIDE TOILET INTERIOR FINISHES AS PER 2006 IBC, SECTION 1210.2 (4' WAINSCOATING FOR SANITARY CLEANING PURPOSES) 6. PROVIDE MOUNTING LOCATION DIMENSIONS FOR DETAIL 4/A-2, SIGNAGE AND DOOR HARDWARE 7. PLEASE CLARIFY DETAIL NOS 1 AND 2/A-1: BOTH DETAILS CALL FOR 5/8" X RATED GYPSUM BOARD TO A POINT 6" ABOVE THE CEILING TILE. BOTH PARTITIONS ARE NOT CALLED OUT TO BE FIRE RATED NOR DOES CODE REQUIRE THEM TO BE SO. THEREFORE, WHY IS "X" RATED SPECIFIED? |
02/12/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The specified drinking fountain does not meet the accessibility requirements as shown in Section 1109.5, IBC 2006. 2. Provide end of run cleanout at mop sink and WC-1. Reference Section 707.4, UPC 2006. |
02/12/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Provide panel and circuit number for all new receptacles. 2. Demonstrate that the panel is not overloaded, on a phase-by-phase basis. |
02/12/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. According to the shell package drawings, two rooftop units, not one, serve the suite. Revise the ventilation notes to indicate the amount of outside air that is to be provided by each unit. Reference Section 106.3.1 |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/07/2008 | SUE REEVES | OUT TO CUSTOMER | Completed |