Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T07CM04510
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/07/2008 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Edmund Marquez - Suzuki Dealership Expansion T07CM04510 Building Plan (1st Review) TRANSMITTAL DATE: January 7, 2008 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\grading\t07cm04510.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents |
| 01/16/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the drawings as needed to clearly show that the design matches the submitted calculations and complies with the code requirements. Reference Sections 101.4 and 102, International Energy Conservation Code 2006. |
| 01/16/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/16/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide location and sizing information for the gutters and downspouts. Reference Section 1106.0, UPC 2006. |
| 01/22/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 02/01/2008 | JASON GREEN | ENGINEERING | REVIEW | Denied | Building plans can not be approved prior to site plan approval. See comments associated with the site plan review. |
| 12/26/2007 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. H/C SIGN TO BE 84" TO BOTTOM OF SIGN 2. IDENTIFY ALL ACCESSIBLE ROUTES FROM STREET TO ENTRY DOORS 3. INDENTIFY ALL ACCESSIBLE ROUTES FROM H/C PARKING SPACES TO ENTRANCE DOORS 4. SHOW ACCESSIBLE ROUTE PATHWAY SLOPES (1-4 AS PER IBC 1104 AND ANSI 117.1 SECTIONS 4 AND 5) 5. PROVIDE COST EVALUATION OF PROJECT SHOWNING COST BREAKDOWN OF ACCESSIBLE EVALUATION, 20%. IBC SECTION 3409.7.1 6. PROVIDE SPECIFICATIONS FOR A HI/LOW WATER COOLER 7. SINK IN ROOM 105 MUST BE ACCESSIBLE; IBC SECTION 1109.3 8. SHOW LARGE SCALE PLANS OF TOILET ROOMS WITH ALL ACCESSIBLE REQUIREMENTS, CLEARANCES AND FIXTURE/ACCESSORY HEIGHTS 9. SHOW TOILET INTERIOR ELEVATIONS SHOWING ALL ACCESSIBILITY FIXTURE/ACCESSORY DIMENSIONS AND HEIGHTS 10. SHOW BREAK ROOM SINK ELEVATION WITH REQUIRED HEIGHTS, CLEARANCES AND ACCESSORIES. 11. ROOF PLAN NOT COMPLETE, SHOW DRAIN SYSTEMS FOR NEW AND EXISTING 12. EXTERIOR ELEVATIONS NOT COMPLETE: A. SHOW ROOF DRAIN ELEMENTS B. SHOW KEYED NOTES C. ELEVATION REFERENCE MARKS DO NOT MATCH FLOOR PLAN REFERNCES 13. PROVIDE WINDOW SCHEDULE 14. DETAIL E-11/A501 NOT SHOWN CLEARLY, ONE REFERENCE ON BUILDING SECTION ONLY AND ELEMENT IS NOT DRAWN ACCORDINGLY AND NOT SHOWN ON FLOOR PLAN 15. PROVIDE SPECS ON WATER HEATER MOUNTING KIT 16. BUILDING SECTION REFERENCES DO NOT CORRESPOND TO FLOOR PLAN REFERENCE MARKS. 17. REFERENCE IN FOUNDATION NOT CALLED OUT IN CALCULATIONS 18. CALCULATION COVER SHEET REFERENCES 2003 IBC, WE ARE IN COMPLIANT WITH 2006 IBC 19. COVER SHEET ALSO LISTS 2000 PSF SOIL BEARING WHILE PAGE 3 OF CALCULATIONS REFERENCES 1,500 PSF 20. PAGE 4 OF CALCULATIONS REFERENCES 2003 IBC, S/B 2006 IBC 21. PROVIDE EXTERIOR LIGHT POLE FOUNDATION CALCULATIONS 22. ANY CHANGES SHOWN IN THE 11 X 17 REDUCED SUBMITTED DRAWINGS ARE TO BE INCORPORATED IN THE 24 X 36 RESUBMITTAL SETS. 23. ARCHITECTURAL DRAWINGS ARE INCOMPLETE AND SHOULD NOT HAVE BEEN SUBMITTED FOR PERMIT. FINISH ALL DRAWINGS PRIOR TO RESUBMITTAL |
| 12/27/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | Impact Fee's Do Apply; West District; 3,150 Square Feet Addition; Retail; Issued Before 1/16/2008 $6,312.20; Issued on and after 1/16/2008 $12,574.40 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/11/2008 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 02/11/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 02/11/2008 | GERARDO BONILLA | REJECT SHELF | Completed |