Permit Number: T07CM04502
Parcel: 10309064B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04502
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/30/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/30/2007 ROBERT SHERRY WATER REVIEW Approved
11/30/2007 RSHERRY1 WWM REVIEW Passed No additional plumbing fixtures
11/30/2007 BIANCA RAMIREZ ENGINEERING REVIEW Approved
12/03/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. FOLLOW ANSI 606 FOR LAVATORY REQUIREMENTS.
2. FOLLOW ANSI 602 FOR DRINKING FOUNTAIN REQUIREMENTS.
3. MUST LIST TYPE OF CONSTRUCTION ON PLANS.
12/03/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t07cm04502 12/3/07

1. Provide power requirements for existing (removed) Heat Pump, and for the new one. If using the same circuit, state so. Demonstrate that conductor and overcurrent protection is properly sized.
12/04/2007 DAVE MANN FIRE REVIEW Approved
12/14/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/14/2007 DROBEY1 ZONING REVIEW Needs Review