Permit Number: T07CM04483
Parcel: 13507450A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04483
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2007 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. NEW 2 HOUR RATED PARTITION ACCEPTED; UL 419. NEED TO CLARIFY FIRE SEALANT AT TOP AND BOTTOM PLATES
2. EXISTING PARTITION MODIFIED TO 2 HOUR RATED IS NOT ACCEPTABLE: A. CONFIRM THE EXISTING 5/8" GYPSUM IS "X" RATED, IF NOT B. ADD 2 LAYERS OF 5/8" GYPSUM BOARD TO EXISTING PARTITION 4" PAST END TOP OF EXISTING GYPSUM BOARD.
3. TOP AND BOTTOM PLATES OF ALL FIRE WALLS, NEW AND EXISTING, MUST BE FIRE SEALED.