Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM04483
Parcel: 13507450A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04483
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2007 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. NEW 2 HOUR RATED PARTITION ACCEPTED; UL 419. NEED TO CLARIFY FIRE SEALANT AT TOP AND BOTTOM PLATES
2. EXISTING PARTITION MODIFIED TO 2 HOUR RATED IS NOT ACCEPTABLE: A. CONFIRM THE EXISTING 5/8" GYPSUM IS "X" RATED, IF NOT B. ADD 2 LAYERS OF 5/8" GYPSUM BOARD TO EXISTING PARTITION 4" PAST END TOP OF EXISTING GYPSUM BOARD.
3. TOP AND BOTTOM PLATES OF ALL FIRE WALLS, NEW AND EXISTING, MUST BE FIRE SEALED.
12/05/2007 GBONILL1 WWM REVIEW Needs Review
12/05/2007 GBONILL1 PLUMBING-COMMERCIAL REVIEW Needs Review
12/05/2007 GBONILL1 FIRE REVIEW Needs Review
12/05/2007 GBONILL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
12/05/2007 GBONILL1 WATER REVIEW Needs Review
12/05/2007 GBONILL1 MECHANICAL-COMMERCIAL REVIEW Needs Review
12/05/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review