Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/04/2007 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. NEW 2 HOUR RATED PARTITION ACCEPTED; UL 419. NEED TO CLARIFY FIRE SEALANT AT TOP AND BOTTOM PLATES 2. EXISTING PARTITION MODIFIED TO 2 HOUR RATED IS NOT ACCEPTABLE: A. CONFIRM THE EXISTING 5/8" GYPSUM IS "X" RATED, IF NOT B. ADD 2 LAYERS OF 5/8" GYPSUM BOARD TO EXISTING PARTITION 4" PAST END TOP OF EXISTING GYPSUM BOARD. 3. TOP AND BOTTOM PLATES OF ALL FIRE WALLS, NEW AND EXISTING, MUST BE FIRE SEALED. |
12/05/2007 | GBONILL1 | WWM | REVIEW | Needs Review | |
12/05/2007 | GBONILL1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
12/05/2007 | GBONILL1 | FIRE | REVIEW | Needs Review | |
12/05/2007 | GBONILL1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
12/05/2007 | GBONILL1 | WATER | REVIEW | Needs Review | |
12/05/2007 | GBONILL1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
12/05/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |