01/22/2008 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Approved PLUMBING PLANS:

1. The City of Tucson has adopted the 2006 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). The plans should reference this code. Remove all references that state "existing" where not appropriate.
2. The supply pipes must be evaluated for sufficient size for controlling excessive flow rates, UPC 610.3. Provide pipe sizes (diameter & length), average pressure and a complete fixture unit schedule UPC 610.8, Table 6-6. IRC P2903.6. Existing water service pipes may require replacement to larger sizes.