Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T07CM04465
Parcel: 107070230

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T07CM04465
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2007 BIANCA RAMIREZ ENGINEERING REVIEW Approved Approved per previously approved development plan S05-109.
11/28/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show the location of the dry well for the ground-mounted evaporative cooler.
2. Clarify how the building drain is to be revised to accomodate the new location of the building sewer.
11/28/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
11/28/2007 STEVE SHIELDS ZONING REVIEW Approved
11/28/2007 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/28/2007 ROBERT SHERRY WATER REVIEW Approved
11/28/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show the location of the ground-mounted evaporative cooler on the site plan.
12/14/2007 DROBEY1 WWM REVIEW Needs Review
12/14/2007 DROBEY1 FIRE REVIEW Needs Review
12/14/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review