Permit Number: T07CM04464
Parcel: 13618001C

Address:
8201 E STELLA RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM04464
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2008 ANDREW CONNOR NPPO REVIEW Passed
04/03/2008 WILDAN 2ND PARTY REVIEW REVIEW Approved
04/11/2008 RBROWN1 ADA REVIEW Denied GENERAL COMMMENT:
1. THIS IS A CITY OF TUCSON PROJECT AND ALL ACCESSIBILITY REQUIREMENTS SHALL BE AS PER ADAAG 1994 EDITION AS A MINIMUM. REMOVE ALL REFERENCES TO ANSI 117.1 COMPLIANCE.
SHEET A1.1
2. DETAILING AND DESIGN OF ACCESSIBLE PARKING SPACES AND PARKING ISLE IS INCOMPLETE. PROVIDE A LARGE SCALE DETAIL SHOWING THE FOLLOWING AND COMPLIANCE WITH ADAAG STANDARDS:
A. PROVIDE ALL DIMENSIONS FOR ACCESSIBLE PARKINGS SPACE AND SIDE ISLE. SLOPES ARE NOT TO BE IN EXCESS OF 2%, ADAAG 4.6. IDENTIFY VAN ACCESSIBLE SPACE. PROVIDE SPOT GRADES OR OTHERWISE CONFIRM SLOPE CONFORMANCE.
B. SHOW LOCATION OF AND PROVIDE AN ELEVATION DETAIL OF ACCESSIBLE PARKING SIGNAGE, ADAAG 4.6.4
C. DELETE THE "L" SHAPED TRUNCATED DOME STRIP AND THE TRAPAZODIAL SHAPE PIECE OF CONCRETE WALK ON THE SIDE OF THE LEFT SIDE PARKING
SPACE. RETAIN THE CONCRETE CURB
D. EXTEND THE MIDDLE PARKING ISLE 4'-6" TO THE EAST AND PROVIDE AN ADAAG 4.7 COMPLIANT CURB RAMP FROM THE EXTENDED ISLE SOUTH TO THE CONCRETE WALKWAY WITH DETECTABLE WARNINGS AS PER 4.7.7.
3. NEW ACCESSIBLE CONCRETE ROUTE TO CONFORM TO ALL REQUIREMENTS OF ADAAG 4.3 AND COT DSD DESIGN STANDARDS. PROVIDE MINIMUM WIDTH OF 4'. PROVIDE SPOT GRADES OR OTHERWISE CONFIRM SLOPE CONFORMANCE.
4. DETAIL 6/FLOOR PLAN:
A. PLEASE PROVIDE WRITTEN APPROVAL FROM OEOP DESCRIBING EXACTLY WHICH STALLS ARE APPROVED TO BE ALTERNATES AND ACCEPTABLE DIMENSIONS.
B. A URINAL IN A 3' X 4' STALL DOES NOT ALLOW A WHEELCHAIR TURNAROUND TO CLOSE THE DOOR. IT NEEDS TO BE IN A STALL THE SAME SIZE AS FOR TOILETS.
5. DETAILS 2,3, AND 4: VERIFY DIMENSIONS AS PER ADAAG FIGURES 28, 29, 30, 31 AND 32
6. CONFIRM ACCESS OPENING CLEARANCES
SHEET A-1.2
7. CLARIFY EXPOSED PLUMBING AND INSULATION REQIREMENTS.
04/15/2008 CPIERCE1 ZONING REVIEW Passed PREVIOUS WORKFLOW - PASSED