Permit Number: T07CM04463
Parcel: 116183810

Address:
325 N GRANDE AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM04463
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2008 ANDREW CONNOR NPPO REVIEW Passed
04/04/2008 WILDAN 2ND PARTY REVIEW REVIEW Approved
04/10/2008 STEVE SHIELDS ZONING REVIEW Passed
04/11/2008 RBROWN1 ADA REVIEW Denied GENERAL COMMMENT:
1. THIS IS A CITY OF TUCSON PROJECT AND ALL ACCESSIBILITY REQUIREMENTS SHALL BE AS PER ADAAG 1994 EDITION AS A MINIMUM. REMOVE ALL REFERENCES TO ANSI 117.1 COMPLIANCE.
SHEET A1.1
2. DETAILING AND DESIGN OF ACCESSIBLE PARKING SPACE, PARKING ISLE AND EXTENDED MARKED ACCESSIBLE PATH IS INCOMPLETE. PROVIDE A LARGE SCALE DETAIL SHOWING THE FOLLOWING AND COMPLIANCE WITH ADAAG STANDARDS:
A. PROVIDE ALL DIMENSIONS FOR ACCESSIBLE PARKINGS SPACE, SIDE ISLE AND EXTENDED ACCESSIBLE ROUTE. SLOPES ARE NOT TO BE IN EXCESS OF 2%, ADAAG 4.6. PROVIDE SPOT GRADES OR OTHERWISE CONFIRM SLOPE CONFORMANCE.
B. SHOW LOCATION OF AND PROVIDE AN ELEVATION DETAIL OF ACCESSIBLE PARKING SIGNAGE, ADAAG 4.6.4
C. PROVIDE AN ADAAG 4.7 COMPLIANT CURB RAMP FROM THE MARKED, EXTENDED ACCESSIBLE ROUTE TO THE EXISTING WALKWAY.
D. SHOW HOW EXISTING ACCESS GATE AND ASSUMED EXTENDED FENCING IS MODIFIED TO ACCOMMODATE ACCESSIBLE ELEMENTS.
3. CONFIRM AND EXPLAIN EXISTING WALK WAY AS AN ACCESSIBLE PATH; DEFINE WIDTH, MATERIAL AND SLOPES. INSURE COMPLIANCE WITH ADAAG 4.3 AND ALL COT, DSD DESIGN STANDARDS. PROVIDE SPOT GRADES OR OTHERWISE CONFIRM EXISTING SLOPE CONFORMANCE.
4. NEW ACCESSIBLE CONCRETE ROUTE TO CONFORM TO ALL REQUIREMENTS OF ADAAG 4.3 AND COT DSD DESIGN STANDARDS. PROVIDE MINIMUM WIDTH OF 4'. PROVIDE SPOT GRADES OR OTHERWISE CONFIRM SLOPE CONFORMANCE.
5. DETAIL 6/FLOOR PLAN:
A. PLEASE WRITTEN APPROVAL FROM OEOP DESCRIBING EXACTLY WHICH STALLS ARE APPROVED TO BE ALTERNATES AND ACCEPTABLE DIMENSIONS.
B. A URINAL IN A 3' X 4' STALL DOES NOT ALLOW A WHEELCHAIR TURNAROUND TO CLOSE THE DOOR. IT NEEDS TO BE IN A STALL THE SAME SIZE AS FOR TOILETS.
6. DETAILS 2,3, AND 4: VERIFY DIMENSIONS AS PER ADAAG FIGURES 28, 29, 30, 31 AND 32
7. EXPLAIN THE DASHED LINES IN THE NEW CONCRETE WALK TO THE BUILDING. EXTERIOR ELEVATION SHOWS RAMPS DOWN. WHAT'SUP?
8. CONFIRM ACCESS OPENING CLEARANCES
SHEET A-1.2
9. CLARIFY EXPOSED PLUMBING AND INSULATION REQIREMENTS.