Permit Number: T07CM04463
Parcel: 116183810

Address:
325 N GRANDE AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04463
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2008 HEATHER THRALL ZONING REVIEW Passed
01/08/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/08/2008 ROBERT SHERRY WATER REVIEW Approved
01/08/2008 SREEVES1 2ND PARTY REVIEW REVIEW Denied December 28, 2007

Metro Permit Express
3619 East Speedway
Suite 101
Tucson, Arizona 85716

RE: Menlo Park ADA Upgrade – 1st REVIEW
CITY OF TUCSON LOG NO. T07CM04463
WILLDAN PROJECT NO. 13881-7083

The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all indicated corrections and revisions to the plans must be made, and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2006 IBC, 2006 IMC, 2006 IECC, 2006 UPC, and the 2005 NEC (with local modifications). Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Roger Brooks.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
U 6 VB 360 No No

Special Inspection is required for the following items:
Welding

GENERAL COMMENTS;
A signed special inspection form from the City of Tucson is required for welding at the time that the plans are resubmitted for a back check. Reference the City of Tucson Submittal Policy.

ARCHITECTURAL COMMENTS:
Sheet G0.1
Please revise the code analysis to reflect the adopted codes of the city.

See accessibility comments


STRUCTURAL COMMENTS:
Reviewed and accepted


PLUMBING COMMENTS:
Reviewed and accepted


MECHANICAL COMMENTS:
Not a part of this review

ELECTRICAL COMMENTS:
Reviewed and accepted


ENERGY CODE COMMENTS:
Not a part of this review


ACCESSIBILITY COMMENTS:
Sheet A1.1
Provide a note that lavatories shall have the hot water lines and traps wrapped with an insulating material or otherwise protected to prevent accidental contact by users. Reference ANSI A117.1 section 606.6

Please clarify the intent of the improvements. Although not dimensioned it does not appear the illustrated improvements will comply with the adopted accessibility guidelines of the city. The water closet compartments are to narrow or to shallow to provide adequate clearances and the urinal stall designed to represent an accessible ambulatory stall is too shallow. Please clarify



Sincerely,

WILLDAN




Roger A. Brooks, C.B.O., V.P.
Division Manager

RAB/jk
01/08/2008 GERRY KOZIOL WWM REVIEW Approved
01/08/2008 WILLDAN ADA REVIEW Denied December 28, 2007

Metro Permit Express
3619 East Speedway
Suite 101
Tucson, Arizona 85716

RE: Menlo Park ADA Upgrade – 1st REVIEW
CITY OF TUCSON LOG NO. T07CM04463
WILLDAN PROJECT NO. 13881-7083

The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all indicated corrections and revisions to the plans must be made, and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2006 IBC, 2006 IMC, 2006 IECC, 2006 UPC, and the 2005 NEC (with local modifications). Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Roger Brooks.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
U 6 VB 360 No No

Special Inspection is required for the following items:
Welding

GENERAL COMMENTS;
A signed special inspection form from the City of Tucson is required for welding at the time that the plans are resubmitted for a back check. Reference the City of Tucson Submittal Policy.

ARCHITECTURAL COMMENTS:
Sheet G0.1
Please revise the code analysis to reflect the adopted codes of the city.

See accessibility comments


STRUCTURAL COMMENTS:
Reviewed and accepted


PLUMBING COMMENTS:
Reviewed and accepted


MECHANICAL COMMENTS:
Not a part of this review

ELECTRICAL COMMENTS:
Reviewed and accepted


ENERGY CODE COMMENTS:
Not a part of this review


ACCESSIBILITY COMMENTS:
Sheet A1.1
Provide a note that lavatories shall have the hot water lines and traps wrapped with an insulating material or otherwise protected to prevent accidental contact by users. Reference ANSI A117.1 section 606.6

Please clarify the intent of the improvements. Although not dimensioned it does not appear the illustrated improvements will comply with the adopted accessibility guidelines of the city. The water closet compartments are to narrow or to shallow to provide adequate clearances and the urinal stall designed to represent an accessible ambulatory stall is too shallow. Please clarify



Sincerely,

WILLDAN




Roger A. Brooks, C.B.O., V.P.
Division Manager

RAB/jk
01/08/2008 DAVE MANN FIRE REVIEW Approved
01/08/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
01/08/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show the source of the hot water that is to supply the lavatories. Reference Section 103.2.3, UPC 2006.
2. Provide a water riser diagram. Reference Section 103.2.3, UPC 2006.
1. Clarify how the secondary drainage from the roof is being accommodated. Reference Section 1101.11, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/09/2008 DELMA ROBEY OUT TO CUSTOMER Completed
01/09/2008 SHANAE POWELL REJECT SHELF Completed