12/26/2007 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T07CM04459

12/31/07 1104 E. WAVERLY ST.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2003 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


SITE PLAN:

1. PLEASE SHOW THE GAS LINE TO THE EXISTING RESIDENCE.

2. WHAT WILL THE AUXILLARY BUILDING BE USED FOR?

FOUNDATION PLANS:

1. PLEASE SHOW VERTICAL #4 WITHIN 1 FOOT OF EACH SIDE OF THE COOLER. AM105.7.1 .

2. CONCRETE NOTE #3 / SHT. 1 ; PLEASE SPECIFY THE SPACING OF THE 8" ANCHOR BOLTS.

FLOOR PLANS:

1. LABEL ALL ROOMS WITH THEIR INTENDED USE.

STRUCTURAL PLANS:

1. SPECIFY DESIGN CRITERIA ON PLANS FOR ROOF DEAD LOAD AND LIVE LOAD. CHECK THE TOTAL LOAD, LL+DL, AT THE TOP OF THE BALES. SEE AM105.5 .

2. THE COOLER ISN'T PERMITTED TO BREAK THE BOX BEAM. AM105.7.6 .

3. HOW DOES THE BOX BEAM CONFORM TO AM105.7.6 . REQUIRED AMOUNT OF BEARING AND LATERAL STABILITY OF THE 2X10s .

4. PROVIDE MANUFACTURER'S DATA FOR PRE-FAB TRUSSES. TRUSS DATA MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. TRUSS DATA SHALL BE CROSS-REFERENCED TO THE FLOOR PLANS.

5. SPECIFY BRACEING OF TRUSSES.

6. DETAIL GABLE END BRACING CONNECTIONS.

ELEVATIONS:

1. SPECIFY THE GABLE MATERIAL IN THE NORTH AND SOUTH ELEVATIONS AND PROVIDE HEIGHT OF THE STRAW BALES.

2. INDICATE ALL MATERIALS USED; STUCCO, CONCRETE BLOCK, GLASS BLOCK, ROOFING SYSTEMS, SIDING,
VENEERS, ETC.

3. NOTE AND SPECIFY ALL ROOF SLOPES APPROPRIATE TO MATERIAL (SEE R905).

4. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY.

SECTIONS - DETAILS - MISC. NOTES:

1. PLEASE PROVIDE A DETAIL FOR THE ATTATCHMENT OF THE STUCCO LATH. AM105.7.9

2. 3 / 1 ; PLEASE PROVIDE A PRESSURE TREATED BOTTOM PLATE.

3. 4 / 1 ; HEADERS REQUIRE 2 FEET BEARING AT EACH SIDE ON STRAW BALES. AM105.7.11 .

4. 6 / 1 ; SPECIFY THE HEIGHT OF THE STRAW BALES,FLOOR TO TOP OF BALES. AM105.6 .

PLUMBING PLANS:

1. PLEASE SPECIFY THE WATER DISTRIBUTION PIPING MATERIAL.

2. PROVIDE AN ISOMETRIC DRAWING OF WASTE LINES. SHOW SIZES OF WASTE LINES, VENTS AND REQUIRED
CLEANOUTS.

3. HOW DOES THE PLUMBING COMPLY WITH AM105.7.11 ?

4. PLEASE PROVIDE A CUT SHEET FOR THE "ARISTON GL6PL"' I COULDN'T FIND THE GL6PL ON LINE.

ELECTRICAL PLANS:

1. PLEASE PROVIDE A RECEPTACLE TO SERVE THE SOUTH YARD. E3801.7 .


IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 8374910.