Permit Number: T07CM04435
Parcel: 13104410A

Address:
5069 E 29TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04435
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/21/2007 MARTIN BROWN FIRE REVIEW Approved
11/21/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Verify the model number, SEER, installed weight, and electrical data for the proposed heat pump.
11/21/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
11/21/2007 ROBERT SHERRY WATER REVIEW Approved
11/21/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/21/2007 JASON GREEN ENGINEERING REVIEW Approved
11/21/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the waste water piping as shown on the plan and the riser diagram.
2. If thebuilding drain is as shown on the plan, provide an upper terminal cleanout.
3. Provide specifications for the "insta-hot".
4. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
11/28/2007 DROBEY1 WWM REVIEW Needs Review
11/28/2007 DROBEY1 ZONING REVIEW Needs Review
11/28/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/28/2007 DELMA ROBEY OUT TO CUSTOMER Completed