Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04435
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/21/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/21/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Verify the model number, SEER, installed weight, and electrical data for the proposed heat pump. |
| 11/21/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/21/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/21/2007 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/21/2007 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 11/21/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the waste water piping as shown on the plan and the riser diagram. 2. If thebuilding drain is as shown on the plan, provide an upper terminal cleanout. 3. Provide specifications for the "insta-hot". 4. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006. |
| 11/28/2007 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 11/28/2007 | DROBEY1 | ZONING | REVIEW | Needs Review | |
| 11/28/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/28/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |