Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM04427
Parcel: 106041670

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM04427
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/10/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t07cm04427 1/10/08

1. Both 3-phase Air curtain circuits are underloaded on the panel schedule. In reworking the calcs, please note that it is not necessary to add 25% for the largest motor, since this is included in "MCA" from the manufacturer.
2. Remove Panel C from load calculations and fault calculations.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/11/2008 DELMA ROBEY APPROVAL SHELF Completed
01/11/2008 DELMA ROBEY OUT TO CUSTOMER Completed
01/11/2008 DELMA ROBEY REJECT SHELF Completed