Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM04427
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/10/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t07cm04427 1/10/08 1. Both 3-phase Air curtain circuits are underloaded on the panel schedule. In reworking the calcs, please note that it is not necessary to add 25% for the largest motor, since this is included in "MCA" from the manufacturer. 2. Remove Panel C from load calculations and fault calculations. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/11/2008 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 01/11/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 01/11/2008 | DELMA ROBEY | REJECT SHELF | Completed |