Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/10/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t07cm04427 1/10/08

1. Both 3-phase Air curtain circuits are underloaded on the panel schedule. In reworking the calcs, please note that it is not necessary to add 25% for the largest motor, since this is included in "MCA" from the manufacturer.
2. Remove Panel C from load calculations and fault calculations.