Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM04427
Parcel: 106041670

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04427
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/21/2007 MARTIN BROWN FIRE REVIEW Approved
11/23/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved NON-SUBSTANTIAL IMPROVEMENT



Date: November 23, 2007

Address: 3325 North 1st Avenue

Permit Numbers: T07OT02647/T07CM04427

Floodplain type: AE

Description of Work: Tenant Improvement





Type permit: Non-residential

Year of construction of existing structure: 1985

Value of work: $ 16,816

Prior permit activity value $ 0

Value of structure: $ 415,242

Increase in Flood Damage Potential: % 4
11/23/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
11/27/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/27/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM04427 11/27/07

1. Clarify circuiting of new Rooftop Unit. Is C-21,23,25 on Power Plan, but is C-19,21,23 on panel schedule.
2. Since MCA is 60A, the unit may not be on a 50A circuit.
3. Please clarify RTU power requirements. On Sheet M-1 both MCA and MOCP are listed at 60A, and normally these figures are not the same.
4. Fill in power for C-4 on panel schedule.
5. Fill in power for C-10 on panel schedule.
6. Provide an electrical circuit for the billiard lights.
7. Clarify voltage. Line diagram and mechanical power requirements call for 120/208V. Panel schedules are 120/240V.
8. Provide available fault current at service.
9. Provide fault calculations for new panel C.
11/27/2007 ROBERT SHERRY WATER REVIEW Approved
11/27/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/27/2007 RSHERRY1 WWM REVIEW Passed No additional plumbing fixtures
11/27/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/04/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/04/2007 DELMA ROBEY OUT TO CUSTOMER Completed