Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04427
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/21/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/23/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | NON-SUBSTANTIAL IMPROVEMENT Date: November 23, 2007 Address: 3325 North 1st Avenue Permit Numbers: T07OT02647/T07CM04427 Floodplain type: AE Description of Work: Tenant Improvement Type permit: Non-residential Year of construction of existing structure: 1985 Value of work: $ 16,816 Prior permit activity value $ 0 Value of structure: $ 415,242 Increase in Flood Damage Potential: % 4 |
| 11/23/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 11/27/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/27/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM04427 11/27/07 1. Clarify circuiting of new Rooftop Unit. Is C-21,23,25 on Power Plan, but is C-19,21,23 on panel schedule. 2. Since MCA is 60A, the unit may not be on a 50A circuit. 3. Please clarify RTU power requirements. On Sheet M-1 both MCA and MOCP are listed at 60A, and normally these figures are not the same. 4. Fill in power for C-4 on panel schedule. 5. Fill in power for C-10 on panel schedule. 6. Provide an electrical circuit for the billiard lights. 7. Clarify voltage. Line diagram and mechanical power requirements call for 120/208V. Panel schedules are 120/240V. 8. Provide available fault current at service. 9. Provide fault calculations for new panel C. |
| 11/27/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/27/2007 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/27/2007 | RSHERRY1 | WWM | REVIEW | Passed | No additional plumbing fixtures |
| 11/27/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 12/04/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/04/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |