Permit Number: T07CM04415
Parcel: 122184340

Review Status: Completed

Review Details: OTHER

Permit Number - T07CM04415
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/14/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Section R4-30-304 D of the Arizona Administrative Code states that a registrant shall sign, date, and seal professional documents that are to be submitted to any regulatory or review body.
2. Provide the size of the existing water meter. Reference Section 103.2.3, UPC 2006.
3. Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson.