Permit Number: T07CM04407
Parcel: 11307242F

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T07CM04407
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/19/2007 LOREN MAKUS ENGINEERING REVIEW Approved
11/19/2007 TERRY STEVENS ZONING REVIEW Approved
11/20/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/20/2007 MARTIN BROWN FIRE REVIEW Approved
11/20/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed Note: All mechanical work deleted by applicant, 11/20/07
11/20/2007 ROBERT SHERRY WATER REVIEW Passed
11/20/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
11/20/2007 GERRY KOZIOL WWM REVIEW Approved
11/20/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed 1. The use of the IPC requires an approved appeal to the building official.
2. Revise and complete the water calculations based on Tables E103.3(2), and 709.1, 2006 IPC. Show the required static lift for the system. Show the method by which the pipes were sized. Reference Section 604.1, IPC 2006.
3. Tucson Water does not provide ¾" water meters. The water demand for the triplex exceeds the maximum demand that Tucson Water allows for a 5/8" water meter (24 GPM). Provide a letter from Tucson Water allowing the use of the existing meter.
4. Show that the addition of the new laundry facilities will not overload the existing water distribution system. Reference Section 102.4, IPC 2006.
5. Provide an upper terminal cleanout for the new fixtures. Reference Section 708.3, IPC 2006.
6. Show that the standpipe receptor for the clotheswasher complies with Section 802.4, IPC 2006.

Note: All plumbing work deleted by applicant, 11/20/07

Final Status

Task End Date Reviewer's Name Type of Review Description
03/13/2008 VFLORES1 OUT TO CUSTOMER Completed