Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - SITE ALL
Permit Number - T07CM04400
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/25/2008 | ANDREW CONNOR | LANDSCAPE | REVIEW | Approv-Cond | |
04/25/2008 | RONALD BROWN | ZONING HC SITE | REVIEW | Passed | COT PROJECT |
04/25/2008 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
04/25/2008 | RBROWN1 | ADA | REVIEW | Denied | SHEET L-0 1. CLARIFY GOVERNING ACCESSIBILITY CODE: ADAAG SHEET L-1 2. SHOW LARGE SCALE DETAIL OF ACCESSIBLE PARKING a. PROVIDE ALL DIMENSIONS b. SHOW HOW ACCESS IS ACHEIVED FROM PARKING AISLE TO RUNNING TRACK c. PROVIDE SPOT GRADES TO SHOW SLOPE COMP-LIANCE, ADAAG SECTION 4.6.3 AND 4.3.7 d. IF RAMP IS REQUIRED, SHOW DETAILS AS PER ADAAG SECTION 4.7 AND 4.8 e. DEFINE "VAN ACCESSIBLE" COMPLIANCE AND DESIGNATE ONE SPACE AS REQUIRED, ADAAG SECTION 4.1.2.5 (b). SHEET L-6 3. DETAIL 8: SHOW A 7'-0" DIMENSION FROM THE BOTTOM OF THE SIGN TO FINISHED GRADE, DOT DESIGN STANDARD. PROVIDE "VAN ACCESSIBLE" SIGN AS REQUIRED. 4. CORRECT FINE AMOUNT TO $518.00 |
04/30/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the site drawing to include the following information: a. the size of the water meter b. the location of the main water lines Reference: City of Tucson Development Standard No. 2-05.0 2.3 and Section 103.2.3, UPC 2006 |
05/14/2008 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: St. Johns Neighborhood Park T07CM04400 Site Plan (2nd Review) TRANSMITTAL DATE: May 14, 2008 COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance for the area of the park expansion only. 2. Per our discussions the lease agreement was to include the parking area. The lease agreement area is not clearly indicated on the plan. 3. This comment was not fully addressed. Provide a fully dimensioned detail of the proposed handicapped parking. This detail shall include maximum allowed surface slopes, location of wheel stops, angle of parking, etc. Identify the required Van Accessible vehicle parking space on the plan. Ensure the accessible access isle is shown on the correct side, passenger side. D.S. 2-02.2.1.A.8 Show the required off-street parking on the plan, including a fully dimensioned layout, parking space size and number, typical parking space details for handicapped and standard spaces and access thereto. If proposing to use existing school parking demonstrate on the plan that there is excess parking available for the park use. Provide a copy of the last approved site plan. 4. This comment was not fully addressed. Provide a detail that includes the materials for lighting, paving, and security; fully dimensioned layout; location; specific type of rack and the number of bicycles it supports. D.S. 2-02.2.1.A.9 Show the required off-street bicycle parking location on the plan. Provide a detail that includes the materials for lighting, paving, and security; fully dimensioned layout; location; specific type of rack and the number of bicycles it supports; and the location and type of directional signage if required. 5. This comment was not addressed. D.S. 2-02.2.1.A.18 Label 12th Avenue as a "MS&R ROUTE". 6. Please clarify what "NEIGHBORHOOD RECREATION "6" is for. The correct development designator is "12" subject to Sec. 3.5.13.2 and Sec. 3.5.13.3.D.S. 2-02.2.1.A.31 Provide the existing and proposed use on the plan. The development designator shown on the plan is incorrect. Per LUC Sec. 2.3.4.2.E.1 and Sec. 2.3.5.2.E.1 the development designator for Neighborhood Recreation is "12" subject to Sec. 3.5.13.2 and Sec. 3.5.13.3. 7. Additional comments may be forth coming depending on how each comment has been addressed. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956. C:\planning\site\t07cm04400-2nd.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents |