Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM04400
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/25/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET E0; SHEET S-1: LIGHT POLE DETAILS 4 AND 5 INDICATE A FOUNDATION THAT DOES NOT MATCH STRUCTURAL DETAIL 3, OR THE STRUCTURAL CALCULATIONS. CLARIFY. 2. SHEET L-3; SHEET S-1: SPREAD FOOTING DETAIL 5 INDICATES A FOOTING THAT DOES NOT MATCH STRUCTURAL DETAIL 2, OR THE STRUCTURAL CALCULATIONS. CLARIFY. |
| 04/25/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/30/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not addressed. Clarify the configuration of the drinking fountain. The specified model number does not match the fountain depicted on the drawing. (i.e. does the proposed drinking fountain, Haws model 3500D, come equipped with a pet fountain?) |
| 04/30/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | Comment not addressed. Provide the size of the existing water meter. |
| 05/12/2008 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: St. Johns Neighborhood Park T07CM04400 Building Plan (2nd Review) TRANSMITTAL DATE: May 14, 2007 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\grading\t07cm04400.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents |
| 05/15/2008 | JASON GREEN | ENGINEERING | REVIEW | Denied | Need a stamped approved site plan prior to building plan approval. |