Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T07CM04400
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/20/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/20/2007 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. NEED FOUNDATION STRUCTURAL CALCULATIONS FOR RAMADA AND 30' LIGHTING STANDARD |
| 11/20/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/21/2007 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: St. Johns Neighborhood Park T07CM04400 Building Plan (1st Review) TRANSMITTAL DATE: November 23, 2007 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\grading\t07cm04400.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents |
| 12/04/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Pole Light Detail 4 on Sheet E0 refers us to Structural Drawings for the pole foundation details. Such drawings not included in this submittal. Note that a Registered Structural Engineer is required to provide the pole and foundation detail and calculations for any pole greater than 30' in height. Cross-Reference Structural comment. 2. It appears that the placement of certain of the lighting poles is in violation of Section 5.4 of the Tucson Lighting Code. This applies to the northwest portion of the track. |
| 12/12/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Clarify the configuration of the drinking fountain. The specified model number does not match the fountain depicted on the drawing. |
| 12/12/2007 | JASON GREEN | ENGINEERING | REVIEW | Denied | The site plan must be approved before the building plan is approved. |
| 12/12/2007 | RSHERRY1 | WWM | REVIEW | Passed | No connection to the sewer |
| 12/12/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 12/12/2007 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide the size of the existing water meter. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/21/2007 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 12/21/2007 | CPIERCE1 | REJECT SHELF | Completed |