Permit Number: T07CM04394
Parcel: 122010740

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04394
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2007 DAVE MANN FIRE REVIEW Approved
11/15/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show the ductwork for the suite along with the balancing data.
11/15/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM04394 11/15/07

1. Ckt C-15,17 powers a line-to-line load on the Power Plan. Does not correspond to panel schedule.
2. Provide conductor size for Dryer circuit.
11/15/2007 ROBERT SHERRY WATER REVIEW Approved
11/15/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/15/2007 BIANCA RAMIREZ ENGINEERING REVIEW Approved
11/15/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The current plumbing code is the 2006 UPC.
2. Provide riser diagrams for the water and the waste and vent sytems.
3. Provide updated water calculations.
11/16/2007 GERRY KOZIOL WWM REVIEW Approved
11/16/2007 TERRY STEVENS ZONING REVIEW Approved
11/16/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/16/2007 THAUSER1 OUT TO CUSTOMER Completed