| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/15/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 11/15/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show the ductwork for the suite along with the balancing data. |
| 11/15/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM04394 11/15/07 1. Ckt C-15,17 powers a line-to-line load on the Power Plan. Does not correspond to panel schedule. 2. Provide conductor size for Dryer circuit. |
| 11/15/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/15/2007 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/15/2007 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 11/15/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The current plumbing code is the 2006 UPC. 2. Provide riser diagrams for the water and the waste and vent sytems. 3. Provide updated water calculations. |
| 11/16/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 11/16/2007 | TERRY STEVENS | ZONING | REVIEW | Approved | |