11/14/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. drawings incomplete, provide site plan plus required building data information
11/14/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide legible drawings (see sheet A7.0) and lettering with a minimum size of 1/8". Reference Section 106.1.1, IBC 2006.
2. Multiple electric convection ovens require a Type II hood. Reference Section 507.2.2, IMC 2006.
11/14/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
11/14/2007 ROBERT SHERRY WATER REVIEW Approved
11/14/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/14/2007 RSHERRY1 WWM REVIEW Passed No additional plumbing fitures
11/14/2007 BIANCA RAMIREZ ENGINEERING REVIEW Approved
12/20/2007 GBONILL1 ZONING REVIEW Needs Review
12/20/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/20/2007 GBONILL1 FIRE REVIEW Needs Review