Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T07CM04358
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/21/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 02/25/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/10/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide information to show that the proposed grease duct insulation system complies with ASTM E 2336. Reference: Section 506.3.10 (1), IMC 2006. 2. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the new and relocated mechanical units. Reference: Section 302.1, IMC 2006. 3. Show the location of the flue for the water heater on the roof equipment plan. Reference: Section 106.3.1, IMC 2006. 4. Provide balancing data for all hoods, make-up air units, and air conditioners. Reference: Sections 106.3.1, 403.3.4, 507.1, 507.13 (as applicable), and 508.1, IMC 2006. 5. Show how the Type I hoods shall comply with the requirements of Section 507.2.1.1, IMC 2006. |
| 03/10/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a floor drain adjacent to the 3-compartment sink per Section 704.3, UPC 2006. |
| 03/19/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/20/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 03/20/2008 | SHANAE POWELL | REJECT SHELF | Completed |