Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM04358
Parcel: 13316033F

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T07CM04358
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2008 GERRY KOZIOL WWM REVIEW Approved
02/25/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
03/10/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information to show that the proposed grease duct insulation system complies with ASTM E 2336. Reference: Section 506.3.10 (1), IMC 2006.
2. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the new and relocated mechanical units. Reference: Section 302.1, IMC 2006.
3. Show the location of the flue for the water heater on the roof equipment plan. Reference: Section 106.3.1, IMC 2006.
4. Provide balancing data for all hoods, make-up air units, and air conditioners. Reference: Sections 106.3.1, 403.3.4, 507.1, 507.13 (as applicable), and 508.1, IMC 2006.
5. Show how the Type I hoods shall comply with the requirements of Section 507.2.1.1, IMC 2006.
03/10/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a floor drain adjacent to the 3-compartment sink per Section 704.3, UPC 2006.
03/19/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/20/2008 CPIERCE1 OUT TO CUSTOMER Completed
03/20/2008 SHANAE POWELL REJECT SHELF Completed