Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved 61 E CONGRESS
T07CM04342

PROVIDE THE ELECTRICAL PLANS IN ORDER TO CHECK REVISIONS,THEY WERE NOT INCLUDED IN THE EXISTING PLANS THAT WERE BROUGHT IN.

R T MAJUTA
DSD ELECTRICAL
3-3-9
03/03/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the basis of the ASHRAE 62-1-2004 ventilation calculations and if the default occupant densities and combined outdoor air rates are not being used, provide justification for the ventilation of the space. Reference: Section 403.2, IMC 2006, as amended by the City of Tucson.
2. Clarify the location of the "storage" space served by AC-3.
3. The zone air distribution effectiveness (Table 6-2, Ez) for a ceiling supply, ceiling return system using gas-fired units is 0.8, not 1.0; include this in the calculations.
4. Complete the ventilation calculations for HP-3; see ASHRAE 62.1-2004 Section 6.2.5.
03/03/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Tucson Water limits a 1-1/2" meter to a maximum demand of 50 GPM. Provide a letter from Tucson Water confirming that the use of a 1-1/2" water meter will be allowed for this project Reference: Sections 610.2 and 610.12, UPC 2006.
2. Water-free urinals are not Code-compliant fixtures per the UPC. Submit an appeal to the Building Official requesting approval to utilize a water-free urinal based on the International Plumbing Code. Reference: Sections 211.0 (insanitary), 301.2, 405.2, 409.0, 601.1, and 1005.0, UPC 2006.
3. Calculate the water demand using the fixture units shown in Tables 6-5 or A-2. Note that flush valve water closets for assembly occupancy have 8 fixture units, not 5 fixture units. Revise the water pipe sizes as required, based on your water pressure calculations. Reference: Section 610.3, UPC 2006.
03/11/2009 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review