Permit Number: T07CM04328
Parcel: 10926009E

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T07CM04328
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2007 DAVE MANN FIRE REVIEW Approved
11/09/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM04328 11/09/07

PLEASE CLARIFY THE FOLLOWING TRANSFORMER ISSUES:
1. Secondary is not protected according to the requirements of NEC Table 450.3 (B).
2. Transformer is 240V on secondary, but provides power for equipment specified for 208V. Please coordinate with Mechanical and clarify.
3. Would like to see a cut sheet for a transformer that takes 277V on the secondary.
11/09/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
11/16/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/16/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/16/2007 GBONILL1 ZONING REVIEW Needs Review
11/16/2007 GBONILL1 ENGINEERING REVIEW Denied
11/16/2007 ROBERT SHERRY WATER REVIEW Passed
11/16/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
11/16/2007 RSHERRY1 WWM REVIEW Passed No connection to the public sewer

Final Status

Task End Date Reviewer's Name Type of Review Description
11/16/2007 GERARDO BONILLA OUT TO CUSTOMER Completed