Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T07CM04328
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/09/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 11/09/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM04328 11/09/07 PLEASE CLARIFY THE FOLLOWING TRANSFORMER ISSUES: 1. Secondary is not protected according to the requirements of NEC Table 450.3 (B). 2. Transformer is 240V on secondary, but provides power for equipment specified for 208V. Please coordinate with Mechanical and clarify. 3. Would like to see a cut sheet for a transformer that takes 277V on the secondary. |
| 11/09/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/16/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 11/16/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/16/2007 | GBONILL1 | ZONING | REVIEW | Needs Review | |
| 11/16/2007 | GBONILL1 | ENGINEERING | REVIEW | Denied | |
| 11/16/2007 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 11/16/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 11/16/2007 | RSHERRY1 | WWM | REVIEW | Passed | No connection to the public sewer |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/16/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |