Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM04327
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/03/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/03/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom fans to prevent recirculation of the air supplied to the restrooms. Reference Section 403.2, IMC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/10/2008 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 03/10/2008 | GERARDO BONILLA | REJECT SHELF | Completed |