Permit Number: T07CM04327
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04327
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/17/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
01/18/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1) Corridor must be rated per IBC 1017 from service corridor to back wall of sales floor.

2) Detail 4 pp A202 please revise to show vertical grab bar between 39" and 41" from rear wall per 2003 ANSI 117.1.

3) Please change all lettering and notes to 1/8" size
01/24/2008 GERRY KOZIOL WWM REVIEW Approved
01/24/2008 MARTIN BROWN FIRE REVIEW Approved
01/31/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
02/08/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006.
2. Show that the specified backflow preventer conforms to the access and clearance requirements of Section 603.2.3, UPC 2006.
02/08/2008 ROBERT SHERRY WATER REVIEW Approved
02/11/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case) Reference Section 106.1.1, IBC 2006.
2. Show the termination point for the condensate drain. Reference Section 307.2.1, IMC 2006, as amended by the City of Tucson.
3. Provide information to show that the design of the trap for the condensate complies with the listing information from the manufacturer of the roof top A/C unit.
4. Comment not addressed on the drawing (i.e. provide a note regarding the materials exposed within the plenum). Materials exposed in plenums shall conform to Section 602.2.1, IMC 2006.
02/20/2008 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/20/2008 GERARDO BONILLA OUT TO CUSTOMER Completed