Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM04327
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04327
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2008 DROBEY1 ZONING REVIEW Needs Review
01/17/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case).
Reference Section 106.1.1, IBC 2006.
2. Show the termination point for the condensate drain.
Reference Section 307.2.1, IMC 2006, as amended by
the City of Tucson.
3. Provide information to show that the design of the trap for the condensate complies with the listing information from the manufacturer of the roof top A/C unit.
4. Comment not addressed on the drawing (i.e. provide a note regarding the material;s exposed within the plenum). Materials exposed in plenums shall conform to Section 602.2.1, IMC 2006.
01/17/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Passed
01/17/2008 ROBERT SHERRY WATER REVIEW Approved
01/17/2008 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) Corridor must be rated per IBC 1017 from service corridor to back wall of sales floor.

2) Detail 4 pp A202 please revise to show vertical grab bar between 39" and 41" from rear wall per 2003 ANSI 117.1.
01/17/2008 DROBEY1 WWM REVIEW Needs Review
01/17/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006.
2. Show that the specified backflow preventer conforms to the access and clearance requirements of Section 603.2.3, UPC 2003.
01/17/2008 DROBEY1 ENGINEERING REVIEW Needs Review
01/17/2008 DROBEY1 FIRE REVIEW Needs Review
01/17/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/17/2008 DELMA ROBEY OUT TO CUSTOMER Completed