Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04327
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/17/2008 | DROBEY1 | ZONING | REVIEW | Needs Review | |
01/17/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006. 2. Show the termination point for the condensate drain. Reference Section 307.2.1, IMC 2006, as amended by the City of Tucson. 3. Provide information to show that the design of the trap for the condensate complies with the listing information from the manufacturer of the roof top A/C unit. 4. Comment not addressed on the drawing (i.e. provide a note regarding the material;s exposed within the plenum). Materials exposed in plenums shall conform to Section 602.2.1, IMC 2006. |
01/17/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
01/17/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
01/17/2008 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Corridor must be rated per IBC 1017 from service corridor to back wall of sales floor. 2) Detail 4 pp A202 please revise to show vertical grab bar between 39" and 41" from rear wall per 2003 ANSI 117.1. |
01/17/2008 | DROBEY1 | WWM | REVIEW | Needs Review | |
01/17/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006. 2. Show that the specified backflow preventer conforms to the access and clearance requirements of Section 603.2.3, UPC 2003. |
01/17/2008 | DROBEY1 | ENGINEERING | REVIEW | Needs Review | |
01/17/2008 | DROBEY1 | FIRE | REVIEW | Needs Review | |
01/17/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/17/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |