Permit Number: T07CM04327
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04327
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2007 STEVE SHIELDS ZONING REVIEW Approved
11/09/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The 2006 International Mechanical Code with Local Amendments is the relevant code for this project.
2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006.
3. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference Section 302.1, IMC 2003.
4. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or above grade in an area capable or absorbing the condensate flow without surface drainage. Reference Section 307.2.1, IMC 2006, as amended by the City of Tucson.
5. Materials exposed in plenums shall conform to Section 602.2.1, IMC 2006.
11/09/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments.
2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006.
3. Specify the type of backflow preventer to be installed on the cold water service after the water meter. Show that the specified backflow preventer conforms to the access and clearance requirements of Sections 103.2.3 and 603.2.3, UPC 2003.
11/09/2007 ROBERT SHERRY WATER REVIEW Approved
11/09/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) Revise font size to 1/8" min.

2) Please indicate current codes as noted. (2006 Ibc, imc, upc; 2003 ANSI 117.1; 2005 NEC.

3) Add vertical grab bar in accessible restrooms per 2003 ANSI 117.1 chapte 6.
11/09/2007 GERRY KOZIOL WWM REVIEW Approved
11/09/2007 DAVE MANN FIRE REVIEW Approved
11/09/2007 JASON GREEN ENGINEERING REVIEW Approved
11/09/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
11/21/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/15/2008 SHANAE POWELL OUT TO CUSTOMER Completed
01/15/2008 CINDY AGUILAR REJECT SHELF Completed