| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/07/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008). 2. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. An appeal to the building official is required if the 2006 International Plumbing code is to be used. 3. Justify the use of indirect wastes for all of the sinks. Reference: Sections 304.0 and 801.3, UPC 2006. 4. Provide a vent for each fixture trap. Reference: Sections 901.0 and 910.1, UPC 2006. 5. Specify the type of backflow prevention device required for each appliance water connection. Reference: Section 603.0, UPC 2006, as amended by the City of Tucson. |
| 04/07/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008). |
| 04/15/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/15/2008 | CPIERCE1 | WWM | REVIEW | Needs Review |