01/18/2008 PAUL MACHADO ENGINEERING REVIEW Denied To: Stephen Robinson DATE: January 18, 2008
Architect
8115 E. Cloud Road
Tucson, Arizona 85750

SUBJECT: New Apartments, 1529 S. Jefferson Ave
Site Plan T07CM04297 (First Review)
T14S, R14E, Section 24

RESUBMITTAL REQUIRED: Site Plan and Drainage Statement.

The Site Plan (SP) and Hydrology Report (DS) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207.
3. Sidewalks are required as part of new development of all properties. All new subdivisions and applications for building permits shall provide five (5) foot wide sidewalks along the entire length of street frontage, whether public or private, of the property in qurestion…….per D.S. 3-01.3.3.A.
4. Please provide property description per D.S. 2-02.2.1.3.
5. Please label lot dimensions and bearings per D.S. 2-02.2.1.5.
6. Provide all existing and proposed buildings and structures, including location, size, height, overhangs, canopies, and use per D.S. 2-02.2.1.6.
7. Show all points of egress and ingress including locations and width of driveways and parking area access lanes (P.A.A.L.) per D.S. 2-02.2.1.11.
8. Please label all vehicular, bicycle, pedestrian, and handicapped circulation clearly identified per D.S. 2-02.2.1.12.
9. Fully dimensioned loading space(s) and maneuvering area(s) per D.S. 2-02.2.1.14.
10. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
11. Show cross section of PAAL with transverse and longitudinal slopes.
12. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19.
13. Sidewalks, curbs and wheelchair ramps are required where applicable per D.S. 3-01.3.0 and installed with "Detectable Warnings" per ADAAG.
14. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
15. Show all fences, walls, or vegetation for screening and sight visibility by type, material, height, location and spacing per D.S. 2-02.2.1.27.
16. Show Site plan number (T07CM04297) on all sheets per D.S. 2-02.2.1.29.
17. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. Contact Environmental Services @ 791-5543 x1212, Andy Vera, for approval of curbside pickup and/or for refuse enclosure questions. Show details of the refuse enclosure on the plans.
18. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
19. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.
20. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice.
21. List the consulting engineer and the owner/developer on the plans with the pertinent information.
22. Add note: "Depress all landscaped areas 6" maximum for water harvesting".

Drainage Statement:
1. Please include a response letter to the comments along with the corrected copies of the DS.
2. A Drainage Statement is a brief description of drainage conditions applicable for a site which are not affected by 100 year flows of 100 cfs, of more……per S.M.D.D.F.M., chap. II, 2.1.2. The DS must be submitted along with the site plan and accepted with the approval of the grading plan.
3. The content and format of the Drainage Statement should follow S.M.D.D.F.M., chap. II, 2.2.
4. Show the project address or administration address and the GP number on the cover sheet of the DS.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:\1529 S. Jefferson Ave site
11/14/2007 MARTIN BROWN FIRE REVIEW Denied Please indicate location of existing fire hydrants, with dimensions to property lines. Additional hydrant may be required, per C.O.T. amendments to the 2006 IFC, section 508.
11/21/2007 TERRY STEVENS ZONING REVIEW Denied TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: T07CM04297
1529 S. Jefferson
Site Plan

TRANSMITTAL: 11/26/07

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. DS 2-02.2.1.2 The legal description is not complete. Should read, "Craycroft Lot 4 Block 6 EXC N 88.38' W98.43'." Revise.

2. DS 2-02.2.1.4 A small, project-location map shall be drawn on the first sheet of the development plan, preferably in the upper right corner. The map should cover approximately one (1) square mile, be drawn at a minimum scale of 3" = 1 mile, and provide the following information.
1. Show the subject property approximately centered within the one (1) square mile area.
2. Identify conditions within the square mile area, such as major streets and
watercourses.
3. Section, township, and range; section corners; north arrow; and the scale will be labeled.

Note: Jefferson Avenue is not half way between Craycroft and Wilmot.

3. DS 2-02.2.1.5 Provide documentation that the applied for lot split (S07-080) has been completed, approved, recorded and finaled by DSD . Provide a copy of the approved lot split plan.

The lot line dimension (250.00') for the north side of the proposed project appears to be incorrect. Revise.

4. DS 2-02.2.1.8 FYI: Handicap parking spaces are not required for residential use unless four or more units are connected. If provided, must meet all requirements of ANSI 117.1-2003.

Provide the maximum slope of the handicap parking space and access aisle per ANSI 117.1-2003 Sec. 502.5. (max. 1:48)

Provide a dimensioned detail for the standard parking space and the parallel parking space.

In the parking space calculations portion of the zoning code information on page sd0 include the number of provided parking spaces.

5. DS 2-02.2.1.9 On detail 2 of sd1 the layout for the bicycle parking spaces is incorrect. Minimum distance between racks is 2'-6". Minimum distance from the front of the bicycle rack is 3'-0". See DS 2-09. Figure 9.

Clearly indicate the location of the required 5'access aisle for the bicycle parking spaces.

6. DS 2-02.2.1.11 Provide a dimension on the site plan for the width of the PAAL.

The 12' wide vehicle use area located east of parking space #9 is required to have curb or barriers along the south side to prevent vehicles from driving onto the adjacent unimproved property. See DS 3-05.2.3.C.1

It appears that a fence or wall is located in the right of way along the west side of the adjoining lot to the north west of this project. Walls or fences are not allowed in the right of way. It also appears to be located in the sight visibility triangle. See engineering comments.

7. DS 2-20.2.1.12 Provide the limits of the indicated joint use access easement. A pedestrian access easement will also be required as it appears the sidewalk for this project crosses over the adjoining property. Provide docket and page recording information for all easements including the easement located over the north west corner of the proposed project.

The indicated leader for the joint use easement is not located properly nor is adequate to provide boundaries of the easement.

The indicated crosswalk cannot be located behind a parking space (#17). Cross walks are to be perpendicular to the PAAL.

The north end of the crosswalk extending past the curbs is part of the pedestrian circulation path and must meet the requirements of a sidewalk. Cannot be asphalt must be concrete.

Truncated domes are required along the handicap access aisle on the landing. Clearly indicate the location of the handicap ramp at the handicap parking space.

Truncated domes are required at the landing of the handicap ramp where the north end of the crosswalk meets the curb. (At the edge of the paving)

8. DS 2-02.2.1.13 If applicable, provide location, size, type and height of existing and proposed signage including billboards,

9. DS 2-02.2.1.25 If applicable, provide existing and proposed lighting layout and type.

10. DS 2-02.2.1.32 Provide location of the refuse container. See engineering comments.

11. Depending on changes to this plan and responses to the above comments additional comments may be forth coming.


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

TLS C:\zoning\siteplan\DSC\T07CM04297.doc
11/26/2007 TERRY STEVENS ZONING HC SITE REVIEW Denied see zoning comments.
11/27/2007 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1. Submit a separate landscape plan per DS 2-07.0. to verify that entire site meets current minimum requirements.

2. Within vehicular use areas, one (1) canopy tree is required for each 10 motor vehicle parking spaces and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1.a

3. Submit an irrigation plan showing irrigation specification design and layout per DS 2-07.5.4.A & DS 2-07.5.4.B including source of irrigation, sleeves for driveways and sidewalks, locations of valves, low-flow bubblers or drip irrigation.

4. Dimension the minimum width and label the square footage measured from the inside of tree planters in the vehicle use area. An unpaved area, which is a minimum of thirty-four (34) square feet in area and four (4) feet in width, must be provided for each canopy tree. Revise planter dimensions as required.
LUC 3.7.2.3.A.1.c, DS 2-07.2.2.A.2.e

5. Additional comments may apply upon submittal of a landscape plan.
11/28/2007 PETER MCLAUGHLIN NPPO REVIEW Denied Submit an Native Plant Preservation plan or, if applicable, submit an Application for Exception to NPPO. If submitting an Application for Exception include acceptable documentation, which clearly indicates that the project will not impact Protected Native Plants. Such documentation includes photographs of the site taken from all sides of the property. Photographs of the site are necessary for NPPO approval per DS 2-15.2.0.C

Final Status

Task End Date Reviewer's Name Type of Review Description
01/23/2008 CINDY AGUILAR OUT TO CUSTOMER Completed