Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM04290
Parcel: 131044000

Address:
4801 E 29TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04290
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2008 JASON GREEN ENGINEERING REVIEW Approved DATE: February 4, 2008
SUBJECT: 4801 E 29th St- Remodeling an existing building (façade, windows, doors and pillars)
TO: Ric Espiriti
LOCATION: T14S R14E Sec23 Ward 3
REVIEWERS: Jason Green, CFM
ACTIVITY: T07CM04290 (Site Plan) and T08OT00282 (Floodplain Use Permit)


SUMMARY: Engineering Division of Development Services Department has received and reviewed the Site Plan (T07CM04290), Floodplain Use Permit (T08OT00282), and the submitted cost estimate for the proposed remodel of the existing building (façade, windows, doors and pillars) for the above referenced property. Engineering Division recommends approval of the Site Plan and Floodplain Use Permit at this time.
CONDITIONS OF PERMIT:

1) The associated improvements are with permit activity number T08OT00282 (Floodplain Use Permit) and T07CM04290 (site plans).
2) Any improvements to the structural building for this project are considered a substantial improvement to an existing floodprone structure if the value of this new improvement is 50% or more than the value of the existing structure in present day value. If the project is determined to be a substantial improvement, and, if it is determined that the lowest floor elevation is below the regulatory floor elevation, a design submittal, and review and acceptance of the submittal for flood proofing will be required and shall conform to City of Tucson floodplain development requirements.
3) Cumulative values shall be accounted for the building structure, so that tracking of the 50% status is current. No person shall repair or alter property in a piecemeal manner so as to avoid the provisions of Section 26-4.1.a.3, Chapter 26-Floodplain and Erosion Hazard Management.
4) The applicant attests to the fact that the plans and documents submitted represent all of the improvements that will be done to the existing building, and that all additions, improvements or repairs to the building are included in the construction plans and/or documents herewith. No other improvements, repairs, reconstruction, additions or remodeling have been made to the structure that is not indicated in the attached plans and/or documents.
5) This permit is specific to the improvements specified as the remodel of an existing building as shown on this plan. It shall not apply to any other structure or property, whether attached or unattached, not specified under this permit.
6) Copies of the improvement plans/permit documents shall be kept in a readily accessible location on site at all times.


If you have any questions, I can be reached at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Development Services
01/17/2008 STEVE SHIELDS ZONING REVIEW Approved
01/17/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
01/17/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
01/17/2008 ROBERT SHERRY WATER REVIEW Approved
01/17/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
01/17/2008 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures
01/17/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
01/17/2008 DAVE MANN FIRE REVIEW Approved
02/06/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/06/2008 DELMA ROBEY OUT TO CUSTOMER Completed