Permit Number: T07CM04279
Parcel: 133181550

Address:
6922 E 4TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T07CM04279
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2007 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T07CM04279

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007 and the 2006 UPC with amendments on 7/10/2007. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

GENERAL NOTES:

" Interior alterations require the installation of smoke alarms if not existing, R313.2.1.

FLOOR PLANS:

1. Show compliance with R303.1 providing (8%) natural (artificial) light into the Family Room (impacted by new construction), or open to an adjoining room per R303.2.
2. Show compliance with R303.1 providing natural ventilation into the Family Room (4%), or approved mechanical ventilation, or open to an adjoining room per R303.2.

STRUCTURAL PLANS:

1. Show the replaced bedroom 8"x10" beam as DF#1 for providing sufficient strength, R301.1.
2. Identify wall panel materials (min 3/8" OSB) Detail G3&4/4, R602.10.6.

SECTIONS - DETAILS:

1. Show all anchor-bolts (Detail G3/4) with 7" embedment into concrete or masonry, R403.1.6.
2. Specify #15 water-resistive barrier over studs of all exterior walls, R703.2.

ELECTRICAL PLANS:

1. Smoke alarms are required outside each separate sleeping area, R313.2.
2. Show a GFCI receptacle outlet within 25' of exterior HVAC equipment, E3801.11

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing and skylights is U=0.75, ceiling R=30 and walls R=13. Show the "R" values of insulation and the "U" factors of the windows and doors on the plans as well as the solar heat gain coefficient SHGC minimum value of 0.40, N1101.2.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/07/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
12/07/2007 SUE REEVES REJECT SHELF Completed