Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM04276
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/06/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/06/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM04276 5/6/08 1. Provide panel and circuit number for all new electrical loads. 2. Provide lighting fixture schedule, with power requirements and lighting source type for both Fixtures A and B. 3. Provide ground fault and short circuit protection for new heat pump. 4. Provide conductor size for new Heat pump. 5. Provide disconnecting means for new heat pump. It does not appear that a wall switch would be appropriate. 6. Provide cut sheets for new lighting fixtures and heat pump. 7. It is not clear from the plans that Fixture A is installed under a porch roof. 8. If the Owner is seeking Certificate of Occupancy for a hair salon, please identify any work station receptacles and attribute the proper electrical load for equipment such as blow dryers, hair dryers, etc. 9. The methodology for load calculations is for dwelling units, not commercial. See NEC Article 220. 10. Demonstrate that no phase of the panel is overloaded. |
| 05/06/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | Per 44CFR 59.1 a floodplain use permit is not needed for bringing a building into compliance with safety issues (ADA complaint bathroom). |
| 05/06/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/20/2008 | GERRY KOZIOL | WWM | REVIEW | Approved |