Permit Number: T07CM04276
Parcel: 12106285A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM04276
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/06/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM04276 5/6/08

1. Provide panel and circuit number for all new electrical loads.
2. Provide lighting fixture schedule, with power requirements and lighting source type for both Fixtures A and B.
3. Provide ground fault and short circuit protection for new heat pump.
4. Provide conductor size for new Heat pump.
5. Provide disconnecting means for new heat pump. It does not appear that a wall switch would be appropriate.
6. Provide cut sheets for new lighting fixtures and heat pump.
7. It is not clear from the plans that Fixture A is installed under a porch roof.
8. If the Owner is seeking Certificate of Occupancy for a hair salon, please identify any work station receptacles and attribute the proper electrical load for equipment such as blow dryers, hair dryers, etc.
9. The methodology for load calculations is for dwelling units, not commercial. See NEC Article 220.
10. Demonstrate that no phase of the panel is overloaded.
05/06/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved Per 44CFR 59.1 a floodplain use permit is not needed for bringing a building into compliance with safety issues (ADA complaint bathroom).
05/06/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/20/2008 GERRY KOZIOL WWM REVIEW Approved