Permit Number: T07CM04276
Parcel: 12106285A

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T07CM04276
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2008 BIANCA RAMIREZ ENGINEERING REVIEW Needs Review Per 44CFR 59.1 a floodplain use permit is not needed for bringing a building into compliance with safety issues (ADA complaint bathroom).
04/21/2008 CPIERCE1 WWM REVIEW Needs Review
04/21/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
04/21/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/21/2008 GLENN MOYER ZONING REVIEW Approved
04/21/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a complete plumbing plan for the restroom revisions and the addition of the shampoo sinks, including water and waste & vent riser diagrams.
2. Determine if the water heater has an expansion tank and a temperature pressure relief. If not, show these revisions on the drawing.
3. Modify the plumbing notes to fit the project.
4. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/21/2008 CPIERCE1 OUT TO CUSTOMER Completed