Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T07CM04276
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/21/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Needs Review | Per 44CFR 59.1 a floodplain use permit is not needed for bringing a building into compliance with safety issues (ADA complaint bathroom). |
| 04/21/2008 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 04/21/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 04/21/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/21/2008 | GLENN MOYER | ZONING | REVIEW | Approved | |
| 04/21/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a complete plumbing plan for the restroom revisions and the addition of the shampoo sinks, including water and waste & vent riser diagrams. 2. Determine if the water heater has an expansion tank and a temperature pressure relief. If not, show these revisions on the drawing. 3. Modify the plumbing notes to fit the project. 4. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/21/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |