Permit Number: T07CM04263
Parcel: 14041055A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04263
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM04263 1/23/08

1. Provide disconnecting means for the Water Heater. Reference NEC 422Part III. Revision Keynote 3 indicates the removal of water heater, but it is still on the electrical panel, circuit 10,12. Please clarify.
2. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. It may work to evoke Section 8.1 Paragraph 4.
01/23/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/23/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/12/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
02/12/2008 CAGUILA1 WWM REVIEW Needs Review