Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04263
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/23/2008 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 01/23/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/23/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 11/30/2007 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/30/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/30/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. All traps shall be protected by a vent. 2. The minimum size of waste and vent piping is 1-1/4". Provide sizes conforming to Table 7-6, UPC 2006. 3. Show how the building sewer connects to the existing site sewer. 4. Provide a design for the water piping. 5. Provide fixture descriptions for all plumbing fixtures. Reference Section 401.1, UPC 2006 6. Provide lavatory faucets complying to to ARS Title 45, Chapter 1, Article 12. The maximum flow rate for lavatory faucets shall be no more than an average of one-half gallon of water per minute at a pressure of eighty PSI or they shall be equipped with a mechanism that causes the faucet to close automatically after delivering no more than one-fourth gallon of water. 7. Show that the floor of the restroom slopes toward the floor drain. Reference Section 411.2, UPC 2006. 8. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006. |
| 11/30/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t07cm04263 11/30/07 1. Revise the minimum font size to 1/8" (all upper case). 2. Demonstrate that the Panel or Service feeding New Panel PL is not overloaded. 3. Provide overcurrent protection for the new feeder. 4. Provide fault current rating of new panel. 5. Provide utility available fault current, and fault calculations for new panel. 6. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. |
| 11/30/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the minimum font size to 1/8" (all upper case). |