Permit Number: T07CM04259
Parcel: 13327001C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04259
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2007 DAVE MANN FIRE REVIEW Approved
11/08/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/08/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved Registrant shall sign and date seal.
11/08/2007 ROBERT SHERRY WATER REVIEW Approved
11/08/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
11/08/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
2. The specified lavatory faucets are designed for a flow rate of 2.2 GPM. According to ARS Title 45, Chapter 1, Article 12, the maximum flow rate for lavatory faucets shall be no more than an average of one-half gallon of water per minute at a pressure of eighty PSI or they shall be equipped with a mechanism that causes the faucet to close automatically after delivering no more than one-fourth gallon of water. Reference Section 402.1, UPC 2003, as amended by the State of Arizona.
11/13/2007 GERRY KOZIOL WWM REVIEW Approved
11/13/2007 STEVE SHIELDS ZONING REVIEW Approved
11/14/2007 LOREN MAKUS ENGINEERING REVIEW Approved Floodplain Use Permit Required

Unable to approval until FUP is submitted and approved.
bramire1
11/13/07
11/15/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review