Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04259
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/08/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
11/08/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
11/08/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Registrant shall sign and date seal. |
11/08/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/08/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/08/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 2. The specified lavatory faucets are designed for a flow rate of 2.2 GPM. According to ARS Title 45, Chapter 1, Article 12, the maximum flow rate for lavatory faucets shall be no more than an average of one-half gallon of water per minute at a pressure of eighty PSI or they shall be equipped with a mechanism that causes the faucet to close automatically after delivering no more than one-fourth gallon of water. Reference Section 402.1, UPC 2003, as amended by the State of Arizona. |
11/13/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
11/13/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
11/14/2007 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | Floodplain Use Permit Required Unable to approval until FUP is submitted and approved. bramire1 11/13/07 |
11/15/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |