Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM04253
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/11/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide a letter from Tucson Water confirming that the use of a 1-1/2" water meter will be allowed for this project (67 fixture units in a flush valve system equates to a demand of 58 GPM) |
04/11/2008 | CPIERCE1 | ENGINEERING | REVIEW | Needs Review | |
04/11/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/11/2008 | CPIERCE1 | ZONING | REVIEW | Needs Review |