12/07/2007 BROWN & ASSOCIATES 2ND PARTY REVIEW REVIEW Denied 06 December 2007
City of Tucson
2nd Party Review
RE: CITY OF TUCSON PERMIT NO. T07M04247
3014 EAST LESTER STREET - ADDITION MASTER BEDROOM
BROWN & ASSOCIATES PLAN CHECK NO: 85701-7203
REVIEWED TO: 2006 IBC, 2006 UPC, 2006 IMC, 2006 IFGC, 2006 IECC, 2005 NEC
The first review comments in this letter require that the applicant respond with a detailed written
response for each comment. Each response shall distinctly describe the actions taken to
resolve the comment issue. Two coordinated and complete sets of revised plans and
documents shall be resubmitted for approval. In addition provide the redlined plans and
documents. Each portion of a plan or document that is revised shall be highlighted with a deltarevision
cloud. The appropriate delta-revision number and date shall be recorded on the plans
and documents. Third and subsequent reviews are charged additionally at the current hourly
rate for administration and plans examination.
Occupancy Occupant Load Construction Area Sq. Ft. Sprinklered Alarms
R-3 NA V-B 340 No Smoke
Special Inspection
Certificate Provided
Required Type
No No NA
Deferred Submittals Required Type
No No NA
*Registered and approved fabricators shall submit a certificate of compliance per IBC 1704.2.2.
GENERAL COMMENTS
1. Review and align code references noted on applicable discipline plans to agree with the
2006 IRC as adopted by the jurisdiction. Reference IBC Section 106.1.1.
06 December 2007
.3014 East Lester Street, Addition Master Bedroom
City of Tucson T07CM04247
Page 2 of 4
ARCHITECTURAL COMMENTS
Sheet A-1
1. Indicate where Key Note 4 is being applied. Reference IRC Section R106.1.
Sheet A-2
1. Provide safety glazing at the window adjacent to the doorway. Also french doors are
required to be safety glazed. Reference IRC Section R308.4.
Sheet A-3
1. Clarify and provide the code reference or listing information for the EPDM Flat Roof
System. Reference Section IRC R904.
Sheet A-4
1. Provide height dimensions for windows and doors. Reference IRC Section R106.1.
Sheet A-5
1. Provide details for flashing on detail A, C, D, E. Reference IRC Section R903.2
ACCESSIBILITY COMMENTS
1. No comments at this time.
STRUCTURAL COMMENTS
Sheet S-1
1. Seismic Design Category C is no longer in use within the City of Tucson. Recalculate the
design using Seismic Design Category B. Reference IRC Section R301.
2. Revise the six by six glue-lam post to Key Note 7. Reference IRC Section R106.1.
3. Indicate the building foundation will be termite pretreated as required by the 2006 IRC.
Reference IRC Section 106.1 and City of Tucson Amendments.
4. Provide nailing schedule on the plans. Reference IRC Table R602.3(1).
5. Define the dead load PSF. Reference IRC Section R106.1.
6. Indicate if the entire addition will be sheathed or if the provisions of IRC Section 602.10
will be applied.
06 December 2007
.3014 East Lester Street, Addition Master Bedroom
City of Tucson T07CM04247
Page 3 of 4
7. Provide complete roof framing showing girders, beams, fasteners and headers over
openings. Identify all post sizes, including Jack and King studs. Reference IRC
R106.1.1.
8. Indicate a minimum of one number four bar in the stem wall of the foundation. Reference
IRC Section R403.1.3.1.
PLUMBING COMMENTS
Sheet P-1
1. Calculations need to be provided for minimum pressure of (40 psi). Reference IRC
P2903.3.
2. Check the design pressure to available pressure. Reference IRC Section P2903.
MECHANICAL COMMENTS
1. No comments at this time.
ELECTRICAL COMMENTS
Sheet E-1
1. Maintain outlet spacing on walls at twelve foot on center. Reference IRC Section
E3801.2.1.
2. Bathroom GFCI circuit can serve only bathroom outlets or one single use bathroom.
Reference IRC Section E3603.4.
3. Outlets shall be ARC fault protected in bedrooms. Reference IRC Section E3802.12.
MODEL ENERGY COMMENTS
1. Provide on the architectural drawings a calculation to determine the percentage of
glazing in the gross area of the exterior walls. Calculations to verify compliance with the
jurisdiction’s adopted Energy Conservation Code are required when the glazing area of
a detached dwelling exceeds 15-percent of the gross area of the exterior walls.
Reference IRC Section N1101.2.1 and N1102.1.
CITY OF TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE
1. No comments at this time.
06 December 2007
.3014 East Lester Street, Addition Master Bedroom
City of Tucson T07CM04247
Page 4 of 4
Sincerely,
BROWN & ASSOCIATES for CITY OF TUCSON
Michael J. Brown, C.B.O.
President
MB:mac